Assigning the DIP-34PA to an Address
Bring the detector into a disarmed alarm loop of the Type 1 of a Signal-10 or to a 1012V power supply. In 6 seconds
the detector’s light emitter will flash four times once per second indicating the detector’s being ready for assigning an
address. Press the light emitter and hold until it lights up. Then press the light emitter again the number of times which is
equal to the required address (1 to 10). In 5 seconds the light emitter will flash the number of times which is equal to the
current address, and then the detector lights up for a half of second.
Auto Assigning the DIP-34PA to a First Vacant Address of a Loop
Bring the DIP-34PA with pressed light emitter into an addressable alarm loop of Type 14 of the Signal-10. In three
seconds the light emitter lights for 1 second and shuts down indicating the address’s being assigned. For example, if the
loop has already contained detectors with addresses 1, 2, 3, and 5 then the current detector will be assigned to the
address of 4.
How to Find Out the Address of the DIP-34PA
Bring the detector into a disarmed alarm loop of the Type 1 of a Signal-10 or to a 1012V power supply. In 6 seconds
the detector’s light emitter will flash four times once per second indicating the detector’s being ready for assigning an
address. Press the light emitter and hold until it lights up. In 5 seconds the light emitter will flash the number of times
which is equal to the current address, and then the detector lights up for a half of second.
DIP-34PA ROUTINE TESTING
Before testing DIP-34PA, please disconnect executive outputs of all system devices and modules that can
release an extinguishing agent or activate light and sound alarms. Notify the fire department and persons
where the audible signals can be heard.
After testing verify that all detectors are ready to operate properly. Then restore operability of all the system
components disconnected before testing and inform the relevant departments about completing the test.
To test the DIP-34PA detector, arm the alarm loop with the connected detector. Before arming the alarm loop should be
in the Norm state indicating this state by light emitter’s flashing once per 8 seconds.
Take a spray can of smoke detector test aerosol and spray some of the test material into the detector. (Or perform a
simplified test just by pressing the detector’s light emitter for 2 to 5 seconds or by lighting the emitter with the laser beam
of a remote laser tester.)
The network controller shall display Fire Alarm message (or Test message in case of a simplified test) for the device with
the address of the DIP-34PA. The detector’s light emitter shall flash doubly each 8 seconds.
If the network controller has displayed no messages mentioned above then the detector is non-functioning and must be
replaced.
Test tools are not provided with the detector and should be purchased aside.
MAINTENANCE
Please test the detector operability annually as said above.
When a Service Required message is received from the detector, remove pollution from the detector smoke chamber.
WARNINGS
To avoid contamination of the detector please DO NOT remove protective cover until the environment is
cleaned up from dust and dirt.
DO NOT remove the detector PCB because this automatically cancels the warranty.
DO NOT mount the detector within the premises where air velocity values exceed 15 m/s.