S2000-2 S2000-2 Programming
71 www.bolid.com
Parameter Description Range
Factory
Value
Forced Open Monitoring
1
Activates monitoring the time of
the door being open
On/Off Off
Held Open Monitoring
1
Activates monitoring for the time
the door is open for
On/Off Off
Held Open Timeout
1
The time needed to expire for
the door which has just been
opened is considered as held
open
1…255 s 20 s
LP 1
Off
Lock Access If Any
Loop Is Armed
LP 2
Specifies alarm loops of the
controller that will lock access
when any of them are armed
(locking based on OR rule)
On/Off
Off
LP 1
Off
Lock Access If All
Loops Are Armed
LP 2
Specifies alarm loops of the
controller that lock access when
all of them are armed (locking
based on AND rule)
On/Off
Off
LED Control Polarity
Provides selecting the active
logic level to turn the LED of the
reader on
Forward (1 active)
Reverse (0 active)
Forward
(1 active)
LED Quiescent Mode
Defines the way the LED lights
in quiescent mode
1 — off
2 — red if any of the
specified below loops is
armed, otherwise the
LED is off
3 — red if all the speci-
fied below alarm loops
are armed, otherwise
the LED is off
4 — red
2
LP 1
On
Indicate
Armed Loops
LP 2
Specifies alarm loops which
being armed causes the LED to
be lit (for 2nd and 3rd LED Qui-
escent Mode – see above)
On/Off
On
LP 1
On
Indicate Loop
Alarms
LP 2
Specifies alarm loops of the
controller which breaking
causes the LED indication
On/Off
On
Sounder Control Polarity
Provides selecting the active
logic level to turn the sounder of
the reader on
Forward (1 active)
Reverse (0 active)
Forward
(1 active)
Access
On/Off On
Door Forced/
Held Open
On/Off On
Loop Alarms
On/Off On
Sound
Alarms
Programming
Enables the reader sounder
signaling for access events,
door being forced and held
open, loop breaking, and key
programming mode entering
respectively
On/Off On
1) The parameter is valid only if the Passage Sensor parameter is set