S2000-2 Maintenance
93 www.bolid.com
Condition Inspection of LOOP, DOOR and EXIT Circuits
To inspect the conditions of electrical circuits, connected to the LOOP, DOOR and EXIT terminals of
the S2000-2 controller, request its ADC readings using the S2000(M) console by doing the follow-
ing:
Power on the S2000(M) console and enter your PIN-code
Select REQUEST INFO command by 3 or 4 console button and
press ENTER, or use 050 console button as the hot key
Select ZONE ADC command by 3 or 4 console button and press
ENTER, or use 020 console button as the hot key
Enter the S2000-2 network address or select the valid value by 3
or 4 console button and press ENTER
Enter gradually the numbers from one to six (or select the proper
value by 3 or 4 console button and press ENTER) and compare
the responded values with the reference values shown below
Table 12. Normal Value Ranges for Some S2000-2 Readings
# The Circuit Identified by This Number Reference Value Range
1
LOOP1 115…127 (8.2 kOhm)
2
LOOP2 115…127 (8.2 kOhm)
3
DOOR1 145…160 (8.2 kOhm)
4
DOOR2 145…160 (8.2 kOhm)
5
EXIT1 145…160 (8.2 kOhm)
6
EXIT2 145…160 (8.2 kOhm)
Each of the circuits mentioned above is considered to be in good condition if the value returned for
the request with the specified number is within the specified range.
v 5 REQUEST INFO
v 51 ZONE ADC
ENTER CODE:_
ADDRESS:_
ENTER LOOP#:_