S2000-2 S2000-2 Programming
87 www.bolid.com
5. Set the Relay Activation Time parameter to a 0.25 ÷ 1s value (which is sufficient to unblock
the turnstile when one person is passing)
6. If Global Anti-passback or Time&Attendance features are to be implemented within a security
system (the S2000-2 operates as a part of networked system) pay attention the access zone
numbers for both readers to be given correctly.
Other configuration parameters are adjusted depending on specific user needs and desires.
Swing-Beam Barrier Mode Programming
In order to program the S2000-2 controller for operating in Swing-beam Barrier mode by means of
UProg Configuration Tool:
1. Select the ‘Swing-beam Barrier’ value in Operation Mode field on the Device tab.
2. The Passage Sensor flags are always active (set on) for this operation mode.
3. Unset the Forced Open Monitoring and Held Open Monitoring parameters.
4. Select the Outputs tab and set the Executive Program to ‘Switch On for a Time’ value for both
the controller relays
5. Set the Relay Activation Time parameter value for the Relay 1 as 5 ÷ 20s (which is sufficient to
lift the swing-beam). If the swing-beam barrier is controlled by the single relay or if the stan-
dard passage time value (30s) must be increased then set the Relay Activation Time parame-
ter for the Relay 1 to a value more than 30s.
6. Set the Relay Activation Time parameter value for the Relay 2 as 5 ÷ 20s (which is sufficient to
lift the swing-beam).
Other configuration parameters are adjusted depending on specific user needs and desires.
Two Sluice Doors Mode Programming
In order to program the S2000-2 controller for operating in Two Sluice Doors mode by means of
UProg Configuration Tool:
1. Select the ‘Two Sluice Mode’ value in Operation Mode field on the Device tab.
2. If Global Anti-passback or Time&Attendance features are to be implemented within a security
system (the S2000-2 operates as a part of networked system) pay attention the access zone
numbers for both readers to be given correctly.
3. The Passage Sensor flags are always active (set on) for this operation mode.
4. If electric strikes are in use as the locking units, set at the Outputs tab
‘Switch On for a Time’ in Executive Program field for both the relays